High-quality, powerful jet fans with optimal dimensions for smallest space requirements. Suitable for supply and extract ventilation or smoke extraction in car parks. Temperature range optional 300 °C/120 min. or 400 °C/120 min. (in smoke extraction operation) or 60 °C in permanent operation.Additional data and accessories
Technical Data
General Information
Ref.-No.: | 04136 |
---|---|
Type: | B-IVAD 355/4/2 R F 400 |
Flow rate free-blowing: | 6400 m³/h |
RPM: | 1435/2900 min-1 |
Number of poles: | 4 / 2 |
Voltage: | 400 V , 3 ph , 50 Hz |
Rated current (FLC) uncontrolled: | 1.25/3.54 A |
Nominal power: | 370/1500 W |
Max. air flow temperature: | 60 °C |
Temperature class: | F400 |
Sound insulated: | |
IP protection category: | 55 |
Insulation class: | H |
PRODUCT_DETAILPAGE_wheel_diameter: | 355 mm |
Weight: | 52,00 kg |
Thrust: | 10 / 38 |
Wiring diagram no.: | 777 |
Acoustic data
Case breakout | 41 dB(A) in 3 m |
---|
Quicklinks
Additional data and accessories
Helios Standorte in Europa.

Helios Ventilatoren GmbH + Co KG
Lupfenstraße 8
78056 Villingen-Schwenningen - DE
Tel.: +49 (0) 7720 / 606-0
Fax: +49 (0) 7720 / 606-166
E-Mail:

Helios Ventilatoren Ges. mbH
Siemensstrasse 15
6063 Rum/Innsbruck
Tel.: +43 (0) 512/26 59 88
Fax: +43 (0) 512/26 59 88 – 85
E-Mail:

Helios Ventilatoren AG
Tannstrasse 4
8112 Otelfingen
Tel.: +41 (0)44 735 36 36
Fax: +41 (0)44 735 36 37
E-Mail:

Helios Ventilateurs
9 rue du gibier
67120 Molsheim
Tel.: +33 (0)3 90 40 48 48
Fax: +33 (0)6 78 03 12 50
E-Mail:

Helios Ventilation Systems
5 Crown Gate, Wyncolls
RoadSeveralls Industrial Park
Colchester, Essex CO4 9HZ
Tel.: +44 (0)1206 228 500
Fax: +44 (0)1206 228 501
E-Mail: