B AVD 500/4 0,55 kW F300
B AVD 500/4 0,55 kW F300
Smoke exhaust axial fan 3-PH, 300°C/120 MIN. 1410 RPM, 0,55 KW


Ref.-No. 02315
Features
High pressure smoke extract fan, temperature class F 300 to DIN 12101 part 3. Short cylindrical casing in galvanised sheet steel covering impeller (motor protrudes at rear) with two flanges on both ends. Dimensions and flange fixing holes to DIN 24155. Impeller with 9 blades from aluminium, high efficiency. Totally enclosed, 3-phase squirrel cage motor. Maintenance-free with low-noise sealed for life ball bearings.Additional data and accessories
Technical Data
General Information
Ref.-No.: | 02315 |
---|---|
Type: | B AVD 500/4 0,55 kW F300 |
Flow rate free-blowing: | 9670 m³/h |
RPM: | 1420 min-1 |
Number of poles: | 4 |
Voltage: | 230 / 400 V , 3 ph , 50 Hz |
Rated current (FLC) uncontrolled: | 2.14/1.23 A |
Nominal power: | 550 W |
Max. air flow temperature: | 40 °C |
Temperature class: | F300 |
IP protection category: | 54 |
Insulation class: | H |
PRODUCT_DETAILPAGE_wheel_diameter: | 500 mm |
Weight: | 39,00 kg |
Wiring diagram no.: | 776 |
Quicklinks
Additional data and accessories
Helios Standorte in Europa.

Helios Ventilatoren GmbH + Co KG
Lupfenstraße 8
78056 Villingen-Schwenningen - DE
Tel.: +49 (0) 7720 / 606-0
Fax: +49 (0) 7720 / 606-166
E-Mail:

Helios Ventilatoren Ges. mbH
Siemensstrasse 15
6063 Rum/Innsbruck
Tel.: +43 (0) 512/26 59 88
Fax: +43 (0) 512/26 59 88 – 85
E-Mail:

Helios Ventilatoren AG
Tannstrasse 4
8112 Otelfingen
Tel.: +41 (0)44 735 36 36
Fax: +41 (0)44 735 36 37
E-Mail:

Helios Ventilateurs
9 rue du gibier
67120 Molsheim
Tel.: +33 (0)3 90 40 48 48
Fax: +33 (0)6 78 03 12 50
E-Mail:

Helios Ventilation Systems
5 Crown Gate, Wyncolls
RoadSeveralls Industrial Park
Colchester, Essex CO4 9HZ
Tel.: +44 (0)1206 228 500
Fax: +44 (0)1206 228 501
E-Mail: