B VARD 500/8/4 F 400
B VARD 500/8/4 F 400
HIGH TEMPERATURE MIXED-FLOW FAN 3-PH, 400°C/120 MIN. 2-speed, Dahlander winding 700/1410 MIN-1, 0,65/2,8 KW


Ref.-No. 02405
Features
High pressure smoke extract fan, temperature class F 400 to DIN 12101 part 3. Cylindrical pre-galvanised sheet-steel casing with a rolled flange at both ends Dimensions and flange fixing holes to DIN 24155, page 2. With guide vanes for improved performance. Mixed flow impeller with 8 spatially curved blades from galvanised steel. Dynamically balanced to class G 6.3 VDI 20060 and DIN ISO 1940. Totally enclosed, 3-phase squirrel cage motor, 2-speed (pole switching with Dahlander windings). Maintenance free with low-noise sealed for life ball bearings.Additional data and accessories
Technical Data
General Information
Ref.-No.: | 02405 |
---|---|
Type: | B VARD 500/8/4 F 400 |
Flow rate free-blowing: | 10430 m³/h |
RPM: | 700/1430 min-1 |
Number of poles: | 8 / 4 |
Voltage: | 400 / 400 V , 3 ph , 50 Hz |
Rated current (FLC) uncontrolled: | 2/4.84 A |
Nominal power: | 550/2200 W |
Max. air flow temperature: | 40 °C |
Temperature class: | F400 |
IP protection category: | 54 |
Insulation class: | F |
PRODUCT_DETAILPAGE_wheel_diameter: | 500 mm |
Weight: | 84,00 kg |
Wiring diagram no.: | 777 |
Quicklinks
Additional data and accessories
Helios Standorte in Europa.

Helios Ventilatoren GmbH + Co KG
Lupfenstraße 8
78056 Villingen-Schwenningen - DE
Tel.: +49 (0) 7720 / 606-0
Fax: +49 (0) 7720 / 606-166
E-Mail:

Helios Ventilatoren Ges. mbH
Siemensstrasse 15
6063 Rum/Innsbruck
Tel.: +43 (0) 512/26 59 88
Fax: +43 (0) 512/26 59 88 – 85
E-Mail:

Helios Ventilatoren AG
Tannstrasse 4
8112 Otelfingen
Tel.: +41 (0)44 735 36 36
Fax: +41 (0)44 735 36 37
E-Mail:

Helios Ventilateurs
9 rue du gibier
67120 Molsheim
Tel.: +33 (0)3 90 40 48 48
Fax: +33 (0)6 78 03 12 50
E-Mail:

Helios Ventilation Systems
5 Crown Gate, Wyncolls
RoadSeveralls Industrial Park
Colchester, Essex CO4 9HZ
Tel.: +44 (0)1206 228 500
Fax: +44 (0)1206 228 501
E-Mail: