B AVD 800/4-35 F600

B AVD 800/4-35 F600

Smoke exhaust axial fan 3-PH, 600°C/120 MIN. 1450 RPM, 7,5 KW

Ref.-No. 02858

Features

Low pressure smoke exhaust axial fan, temperature class F 600 to EN 12101 pt.3. For applications with air flow temperatures of 600 °C/120 minutes (one-time). Cylindrical casing from galvanised sheet steel with a rolled flange at both ends. Dimensions and flange fixing holes to DIN 24155, page 3., for direct in-line installation in ducting. With guide vanes for improved performance. High-performance impeller with 5 profiled blades from hot-dip galvanized steel. Welded hot-dip galvanized steel impeller. Dynamically balanced to EN 1940-1, class G 6.3 IEC-three phase a.c motor, protection to IP 55. Suitable for installation within and outside of the fire zone. The motor is encapsulated and externally ventilated by one or two supply air fans B KLG. Isolation class H. Cable to the terminal box with fire resistant sheathing. Depending on the installation situation, relubrication intervals or change of bearings must be observed.

Technical Data

General Information
Ref.-No.:02858
Type:B AVD 800/4-35 F600
Flow rate free-blowing:35010 m³/h
RPM:1460 min-1
Number of poles:4
Voltage:400 / 690 V , 3 W , 50 ph
Rated current (FLC) uncontrolled:13.9 A
Nominal power:7500 W
Max. air flow temperature:40 °C
Temperature class:F600
IP protection category:54
Insulation class:H
PRODUCT_DETAILPAGE_wheel_diameter:800
Weight:190 kg
Wiring diagram no.:776