B AVD 500/4 0,75 kW F400

B AVD 500/4 0,75 kW F400

Smoke exhaust axial fan 3-PH, 400°C/120 MIN. 1410 MIN-1, 0,75 KW

Ref.-No. 02402

Features

Smoke exhaust axial fan, temperature class F 400 to DIN 12101 part 3. Short cylindrical casing in galvanised sheet steel covering impeller (motor protrudes at rear) with two flanges on both ends. Dimensions and flange fixing holes to DIN 24155. Impeller with 9 blades from aluminium, high efficiency. Totally enclosed, 3-phase squirrel cage motor. Maintenance-free with low-noise sealed for life ball bearings.

Technical Data

General Information
Ref.-No.:02402
Type:B AVD 500/4 0,75 kW F400
Flow rate free-blowing:9667 m³/h
RPM:1420 min-1
Number of poles:4
Voltage:230 / 400 V , 3 W , 50 ph
Rated current (FLC) uncontrolled:2.82/1.62 A
Nominal power:750 W
Max. air flow temperature:40 °C
Temperature class:F400
IP protection category:55
Insulation class:H
PRODUCT_DETAILPAGE_wheel_diameter:500
Weight:38 kg
Wiring diagram no.:776